   Introduction
   1. Background
   2. Supplement
   3. Conveyances
   4. RTF
   5. Schedule
   Appendices

Appendix 9: Preliminary RTF basis of design

A. Design Flow Rate  
   Storm frequency, year 1
   Storm frequency, hour 2
   Rainfall interval, minutes 15
   Peak instantaneous flow rate (cfs) 330
   Peak influent design flow rate, cubic feet per second (cfs) 495
   Total design storm volume, million gallons (MG) 14.8
B. Trash Rack  
   Type Manual
   Location Influent stilling well
   Clear opening, inches 4
   Number of units 2 (one vertical, one inverted at 60°)
   Materials of construction Aluminum or stainless steel
   Length, feet 42
   Height, feet 4 (vertical), 7 (inverted)
C. Grit/Debris Removal Facilities  
   Type Grit sump
   Location Influent stilling well
   Grit Sump Dimensions, length x width x depth, feet 42 x 5 x 3
   Removal mechanism Clamshell with overhead bridge crane
   Disposal Truck hauler
   Estimated grit/debris quantity, cubic yards/year 535
D. Influent Pumps  
   Pump type Mixed flow
   Number of units 3 (2 operating, 1 standby)
   Capacity per unit, cfs 165
   TDH, feet 27
   Pump column diameter, inches 54
   Pump suction bell diameter, inches 78
   Motor horsepower 600
   Drive type Constant speed
   Motor voltage, volts 460
   Pump speed, rotations per minute (rpm) 295
   Potential manufacturers Fairbanks Morse, Patterson
E. Vortex Solids Separator Influent Gates  
   Type Motor-operated sluice gate
   Materials of construction Fabricated stainless steel
   Number 2
   Size, width x height, inches 72 x 72
   Potential manufacturers Rodney Hunt, Fontaine
F. Vortex Solids Separator  
   Type USEPA swirl concentrator
   Design settleable solids recovery, percent 90
   Number of units 9
   Capacity per unit, cfs 170
   Materials of construction Reinforced concrete basin with coated steel internals
   Inlet channel, Dl, inches 72x72
   Chamber diameter, D2, feet 42
   Scum ring diameter, D3, feet 28
   Overflow weir diameter, D4, feet 23.3
   Chamber depth, H, feet 10.5
   Basin volume, cubic feet 12,640
   Underflow pipe diameter, inches 24
   Overflow pipe diameter, inches 72
G. Underflow Control/Dewatering Pump  
   Underflow rate, cfs (maximum) 16.5
   Percent of design peak influent flow 5
   Discharge Force main to main interceptor sewer
   Number of force mains 2
   Force main diameter, inches 16
   Pump type Submersible, recessed impeller, grit handling
   Number of units 3 (2 installed, 1 spare)
   Design dewatering duration (one pump operating), hours 48
   Design points  
   - Underflow control rate, gallons per minute (gpm) 3,700
   - Dewatering rate, gpm 2,930
   Pump discharge diameter, inches 10
   Motor horsepower 60
   Pump speed, RPM 1,780
   Drive type Variable frequency drive
   Potential manufacturers Hayword Gordon, Wemco
H. Disinfection Chemical Storage Equipment  
   1. Chlorination  
   a. Chlorination Chemical  
     Type Liquid Sodium Hypochlorite
     Design chemical strength, percent 10
   b. Chlorination Chemical Storage  
     Type Vertical, cross-linked HOPE
     Number of tanks 2
     Nominal capacity, gallons (each tank) 2000
     Working volume, gallons (each tank) 1,500
     Potential tank manufacturer Nalgene, Chem-Tainer
   2. Dechlorination  
   a. Dechlorination Chemical  
     Type Liquid Sodium Metabisulfite
     Design chemical strength, percent 38
   b. Dechlorination Chemical Storage  
     Type Vertical, cross-linked HDPE
     Number of tanks 2
     Nominal capacity, gallons (each tank) 500
     Working volume, gallons (each tank) 450
     Potential tank manufacturer Nalgene, Chem-Tainer
I. Disinfection Chemical Feed Equipment  
   1. Chlorination  
   Dosage, mg/L 14
   Chlorination chemical feed point Chlorination chamber of disinfection tank
   Type of chemical feed pumps Peristaltic, variable speed
   Potential pump manufacturers Watson Marlow/Bredel
   Number of on-line chemical feed pumps 2
   Number of installed backup chemical feed pumps 2
   Total number of chemical feed pumps 4
   Design feed rate, gallons per hour 630
   Chemical feed pump capacity, gallons per hour 1,386
   Motor horsepower 2
   Number of chemical inductors 2
   Potential chemical inductor manufacturer USFilter/Waterchamp
   Motor horsepower 7.5
2. Dechlorination  
   Dosage, mg/L 11
   Dechlorination Dechlorination chamber of disinfection tank
   Type of chemical feed pumps Peristaltic, variable speed
   Potential manufacturers Watson Marlow/Bredel
   Number of on-line chemical feed pumps 1
   Number of installed backup chemical feed pumps 1
   Total number of chemical feed pumps 2
   Design feed rate, gallons per hour 342
   Chemical feed pump capacity, gallons per hour 528
   Motor horsepower 1.5
   Number of chemical inductors 2
   Potential chemical inductor manufacturers USFilter/Waterchamp
   Motor horsepower 7.5
3. Disinfection control  
   Type Oxidation reduction potential
   Potential manufacturers USFilter/Stranco
   4. Sample pumps for disinfection control  
   a. Chlorination  
     Sample point location Chlorination chamber of disinfection tank
     Type of sample pump Non-clog, submersible
     Potential pump manufacturers Flygt Pumps
     Number of sample pumps for chlorination control 2 (1 uninstalled spare)
     Design capacity range 45 to 75 gpm
     Motor horsepower 1.8
   b. Dechlorination  
     Sample point location Dechlorination chamber of disinfection tank
     Type of sample pump Non-clog, submersible
     Potential pump manufacturers Flygt Pumps
     Number of sample pumps for dechlorination control 2 (1 uninstalled spare)
     Design capacity range 45 to 75 gpm
     Motor horsepower 1.8
J. High-rate disinfection tank  
   Type Cast-in-place, reinforced concrete, plug flow
   Approximate area, square feet 12,000
   Design water depth, feet 16.8
   Approximate volume, cubic feet 134,000
   Length to width ratio 31 to 1
   Chlorination contact time @ 330 cfs, minutes 5.0
   Dechlorination contact time @ 330 cfs, minutes 1.0
   Method of washdown Tipping buckets
   Potential tipping bucket manufacturers Waste Tech, John Meunier, GNA
K. Outfall  
   Type Reinforced concrete culvert with flexible flap valves
   Location Disinfection tank effluent
   Design flow rate, cfs 495
   Dimensions, length x width x depth, feet 49 x 16 x 11
L. Facilities Information  
1. Building  
   Foundation type Reinforced concrete footing, walls, and slabs
   Approximate area, square feet 24 000
   Architectural features Concrete masonry block walls, flat roof
   Roof type Precast concrete T-beams and planks
2. Electrical/Instrumentation  
   Incoming power information Primary metering, dual/redundant service with electrically operated main and tie fused switches
   Primary voltage, kilovolts 13.2
   Switchgear voltage, kilovolts 13.2
   Facility distribution Individual transformers for each influent pump and dual/redundant transformers for the remaining plant load with electrically operated main fused switches and breakers to a main switchboard
   Controls Programmable logic controller based controls with coordinated communication with existing/planned County systems
3. Heating  
   Type Natural gas-fired, pulse-type hydronic boilers
   Estimated heating load, million BTUs 3.0
4. Ventilation  
   RTF air changes per hour (ACPH) during event and occupied, wet areas 12
   RTF ACPH during nonevent, wet well only 2
   Storage Tank ACPH during event and occupied 6
   Wet area exhaust To odor control system
5. Odor Control System  
   Type Activated carbon multiple canister system utilizing water regenerable carbon
   Number of vessels 4
   Unit dimensions, length x width x height, feet 32x6x11
   Total air flow rate, cubic feet per minute 116,000
   Unit capacity, cubic feet per minute 30,000
   Potential manufacturers Calgon Carbon
6. Noise Control Measures  
   Reduced noise generation will be criteria in selecting all equipment  
   Wall construction adjacent to spaces containing noise generating equipment (pump room, odor control room, etc.) will employ noise dampening measures (acoustical block, noise dampeners, etc.)  
   Acoustical louvers will be used for inlet louvers connected to spaces containing noise generating equipment  
   Rooftop equipment (i.e., supply fans) will be housed in sound attenuating enclosures  
M. Emergency Controlled Diversion  
   Type Reinforced concrete culvert with flexible flap valves
   Location Influent sump
   Design flow rate, cfs 1000