A. Design Flow Rate
|
|
|
Storm frequency, year
|
1
|
|
Storm frequency, hour
|
2
|
|
Rainfall interval, minutes
|
15
|
|
Peak instantaneous flow rate (cfs)
|
330
|
|
Peak influent design flow rate, cubic feet per second (cfs)
|
495
|
|
Total design storm volume, million gallons (MG)
|
14.8
|
|
B. Trash Rack
|
|
|
Type
|
Manual
|
|
Location
|
Influent stilling well
|
|
Clear opening, inches
|
4
|
|
Number of units
|
2 (one vertical, one inverted at 60°)
|
|
Materials of construction
|
Aluminum or stainless steel
|
|
Length, feet
|
42
|
|
Height, feet
|
4 (vertical), 7 (inverted)
|
|
C. Grit/Debris Removal Facilities
|
|
|
Type
|
Grit sump
|
|
Location
|
Influent stilling well
|
|
Grit Sump Dimensions, length x width x depth, feet
|
42 x 5 x 3
|
|
Removal mechanism
|
Clamshell with overhead bridge crane
|
|
Disposal
|
Truck hauler
|
|
Estimated grit/debris quantity, cubic yards/year
|
535
|
|
D. Influent Pumps
|
|
|
Pump type
|
Mixed flow
|
|
Number of units
|
3 (2 operating, 1 standby)
|
|
Capacity per unit, cfs
|
165
|
|
TDH, feet
|
27
|
|
Pump column diameter, inches
|
54
|
|
Pump suction bell diameter, inches
|
78
|
|
Motor horsepower
|
600
|
|
Drive type
|
Constant speed
|
|
Motor voltage, volts
|
460
|
|
Pump speed, rotations per minute (rpm)
|
295
|
|
Potential manufacturers
|
Fairbanks Morse, Patterson
|
|
E. Vortex Solids Separator Influent Gates
|
|
|
Type
|
Motor-operated sluice gate
|
|
Materials of construction
|
Fabricated stainless steel
|
|
Number
|
2
|
|
Size, width x height, inches
|
72 x 72
|
|
Potential manufacturers
|
Rodney Hunt, Fontaine
|
|
F. Vortex Solids Separator
|
|
|
Type
|
USEPA swirl concentrator
|
|
Design settleable solids recovery, percent
|
90
|
|
Number of units
|
9
|
|
Capacity per unit, cfs
|
170
|
|
Materials of construction
|
Reinforced concrete basin with coated steel internals
|
|
Inlet channel, Dl, inches
|
72x72
|
|
Chamber diameter, D2, feet
|
42
|
|
Scum ring diameter, D3, feet
|
28
|
|
Overflow weir diameter, D4, feet
|
23.3
|
|
Chamber depth, H, feet
|
10.5
|
|
Basin volume, cubic feet
|
12,640
|
|
Underflow pipe diameter, inches
|
24
|
|
Overflow pipe diameter, inches
|
72
|
|
G. Underflow Control/Dewatering Pump
|
|
|
Underflow rate, cfs (maximum)
|
16.5
|
|
Percent of design peak influent flow
|
5
|
|
Discharge
|
Force main to main interceptor sewer
|
|
Number of force mains
|
2
|
|
Force main diameter, inches
|
16
|
|
Pump type
|
Submersible, recessed impeller, grit handling
|
|
Number of units
|
3 (2 installed, 1 spare)
|
|
Design dewatering duration (one pump operating), hours
|
48
|
|
Design points
|
|
|
- Underflow control rate, gallons per minute (gpm)
|
3,700
|
|
- Dewatering rate, gpm
|
2,930
|
|
Pump discharge diameter, inches
|
10
|
|
Motor horsepower
|
60
|
|
Pump speed, RPM
|
1,780
|
|
Drive type
|
Variable frequency drive
|
|
Potential manufacturers
|
Hayword Gordon, Wemco
|
|
H. Disinfection Chemical Storage Equipment
|
|
|
1. Chlorination
|
|
|
a. Chlorination Chemical
|
|
|
Type
|
Liquid Sodium Hypochlorite
|
|
Design chemical strength, percent
|
10
|
|
b. Chlorination Chemical Storage
|
|
|
Type
|
Vertical, cross-linked HOPE
|
|
Number of tanks
|
2
|
|
Nominal capacity, gallons (each tank)
|
2000
|
|
Working volume, gallons (each tank)
|
1,500
|
|
Potential tank manufacturer
|
Nalgene, Chem-Tainer
|
|
2. Dechlorination
|
|
|
a. Dechlorination Chemical
|
|
|
Type
|
Liquid Sodium Metabisulfite
|
|
Design chemical strength, percent
|
38
|
|
b. Dechlorination Chemical Storage
|
|
|
Type
|
Vertical, cross-linked HDPE
|
|
Number of tanks
|
2
|
|
Nominal capacity, gallons (each tank)
|
500
|
|
Working volume, gallons (each tank)
|
450
|
|
Potential tank manufacturer
|
Nalgene, Chem-Tainer
|
|
I. Disinfection Chemical Feed Equipment
|
|
|
1. Chlorination
|
|
|
Dosage, mg/L
|
14
|
|
Chlorination chemical feed point
|
Chlorination chamber of disinfection tank
|
|
Type of chemical feed pumps
|
Peristaltic, variable speed
|
|
Potential pump manufacturers
|
Watson Marlow/Bredel
|
|
Number of on-line chemical feed pumps
|
2
|
|
Number of installed backup chemical feed pumps
|
2
|
|
Total number of chemical feed pumps
|
4
|
|
Design feed rate, gallons per hour
|
630
|
|
Chemical feed pump capacity, gallons per hour
|
1,386
|
|
Motor horsepower
|
2
|
|
Number of chemical inductors
|
2
|
|
Potential chemical inductor manufacturer
|
USFilter/Waterchamp
|
|
Motor horsepower
|
7.5
|
|
2. Dechlorination
|
|
|
Dosage, mg/L
|
11
|
|
Dechlorination
|
Dechlorination chamber of disinfection tank
|
|
Type of chemical feed pumps
|
Peristaltic, variable speed
|
|
Potential manufacturers
|
Watson Marlow/Bredel
|
|
Number of on-line chemical feed pumps
|
1
|
|
Number of installed backup chemical feed pumps
|
1
|
|
Total number of chemical feed pumps
|
2
|
|
Design feed rate, gallons per hour
|
342
|
|
Chemical feed pump capacity, gallons per hour
|
528
|
|
Motor horsepower
|
1.5
|
|
Number of chemical inductors
|
2
|
|
Potential chemical inductor manufacturers
|
USFilter/Waterchamp
|
|
Motor horsepower
|
7.5
|
|
3. Disinfection control
|
|
|
Type
|
Oxidation reduction potential
|
|
Potential manufacturers
|
USFilter/Stranco
|
|
4. Sample pumps for disinfection control
|
|
|
a. Chlorination
|
|
|
Sample point location
|
Chlorination chamber of disinfection tank
|
|
Type of sample pump
|
Non-clog, submersible
|
|
Potential pump manufacturers
|
Flygt Pumps
|
|
Number of sample pumps for chlorination control
|
2 (1 uninstalled spare)
|
|
Design capacity range
|
45 to 75 gpm
|
|
Motor horsepower
|
1.8
|
|
b. Dechlorination
|
|
|
Sample point location
|
Dechlorination chamber of disinfection tank
|
|
Type of sample pump
|
Non-clog, submersible
|
|
Potential pump manufacturers
|
Flygt Pumps
|
|
Number of sample pumps for dechlorination control
|
2 (1 uninstalled spare)
|
|
Design capacity range
|
45 to 75 gpm
|
|
Motor horsepower
|
1.8
|
|
J. High-rate disinfection tank
|
|
|
Type
|
Cast-in-place, reinforced concrete, plug flow
|
|
Approximate area, square feet
|
12,000
|
|
Design water depth, feet
|
16.8
|
|
Approximate volume, cubic feet
|
134,000
|
|
Length to width ratio
|
31 to 1
|
|
Chlorination contact time @ 330 cfs, minutes
|
5.0
|
|
Dechlorination contact time @ 330 cfs, minutes
|
1.0
|
|
Method of washdown
|
Tipping buckets
|
|
Potential tipping bucket manufacturers Waste
|
Tech, John Meunier, GNA
|
|
K. Outfall
|
|
|
Type
|
Reinforced concrete culvert with flexible flap valves
|
|
Location
|
Disinfection tank effluent
|
|
Design flow rate, cfs
|
495
|
|
Dimensions, length x width x depth, feet
|
49 x 16 x 11
|
|
L. Facilities Information
|
|
|
1. Building
|
|
|
Foundation type
|
Reinforced concrete footing, walls, and slabs
|
|
Approximate area, square feet
|
24 000
|
|
Architectural features
|
Concrete masonry block walls, flat roof
|
|
Roof type
|
Precast concrete T-beams and planks
|
|
2. Electrical/Instrumentation
|
|
|
Incoming power information
|
Primary metering, dual/redundant service with electrically operated main and tie fused switches
|
|
Primary voltage, kilovolts
|
13.2
|
|
Switchgear voltage, kilovolts
|
13.2
|
|
Facility distribution
|
Individual transformers for each influent pump and dual/redundant transformers for the remaining plant load with electrically operated main fused switches and breakers to a main switchboard
|
|
Controls
|
Programmable logic controller based controls with coordinated communication with existing/planned County systems
|
|
3. Heating
|
|
|
Type
|
Natural gas-fired, pulse-type hydronic boilers
|
|
Estimated heating load, million BTUs
|
3.0
|
|
4. Ventilation
|
|
|
RTF air changes per hour (ACPH) during event and occupied, wet areas
|
12
|
|
RTF ACPH during nonevent, wet well only
|
2
|
|
Storage Tank ACPH during event and occupied
|
6
|
|
Wet area exhaust
|
To odor control system
|
|
5. Odor Control System
|
|
|
Type
|
Activated carbon multiple canister system utilizing water regenerable carbon
|
|
Number of vessels
|
4
|
|
Unit dimensions, length x width x height, feet
|
32x6x11
|
|
Total air flow rate, cubic feet per minute
|
116,000
|
|
Unit capacity, cubic feet per minute
|
30,000
|
|
Potential manufacturers
|
Calgon Carbon
|
|
6. Noise Control Measures
|
|
|
Reduced noise generation will be criteria in selecting all equipment
|
|
|
Wall construction adjacent to spaces containing noise generating equipment (pump room, odor control room, etc.) will employ noise dampening measures (acoustical block, noise dampeners, etc.)
|
|
|
Acoustical louvers will be used for inlet louvers connected to spaces containing noise generating equipment
|
|
|
Rooftop equipment (i.e., supply fans) will be housed in sound attenuating enclosures
|
|
|
M. Emergency Controlled Diversion
|
|
|
Type
|
Reinforced concrete culvert with flexible flap valves
|
|
Location
|
Influent sump
|
|
Design flow rate, cfs
|
1000
|